 European and international reference standards applicable to oil-immersed transformers.
 How do I contact France Transfo's customer service?
 How can I get hold of a copy of the drawings for my transformer?
 Where can I find a catalogue of France Transfo's products? Where can I find documents on these products?
 Definition of the Self-Protected Transformer
 Role of a DGPT2 or DMCR protection device in a transformer
 Monitoring functions of a DGPT2 or DMCR protection device
 European and international reference standards applicable to the oils used in France Transfo’s range of oil-immersed transformers
 General instructions for installation of an oil immersed transformer
Ensure that machine characteristics shown on the rating plate correspond with
installation conditions: primary voltage(s), tapping links.
This plate may be moved and attached to any side of the tank so that it is visible
once the machine is in position.
In general, installation must comply with the requirements of IEC Standard
71-1, 2 and 3 in relation to insulation co-ordination.
E.g.: case of overhead-underground connection to be protected by lightning
arresters installed at both ends of the HV cable.
Unit to be installed at a maximum altitude of 1000 m, unless otherwise specified
with order, because air rarefaction adversely affects cooling of the windings.
Unless otherwise specified with order, transformers of standard design are
sized in accordance with IEC Standard 76 for the following ambient
temperatures:
- maximum : 40°C
- average daily : 30°C
- average annual : 20°C
- minimum : – 25°C
When the transformer is live, the ambient temperature inside the plantroom must
comply with the above values, unless the transformer has been specially designed
on the basis of a particular specification.
 Defining the height and cross-sections of ventilation openings in the transformer room
 Dielectric fluid retention system
 Starting or inrush current
 Is the CE Marking applicable to the France Transfo transformers?
 What does the set of initials with 2 or 4 letters mean to define the cooling system for oil immersed transformer ?
  Our commitment
 


an After Sales hot-line is available for our customers 24 hours, 7 days a week : 33 3 87 70 57 72

a 5-year guarantee for Trihal
  Environment
 


A real environment protection policy
:

Certified environmental system (AFAQ ISO 14001)
PCB transformer replacement offer
Trihal cast-resin transformer offer
© 2006 France Transfo